Protected premises fire alarm system this section should be used for department of correctional services projects. This section covers a system which has one or more microprocessor based fire ala



Download 306.74 Kb.
Page1/3
Date conversion08.07.2018
Size306.74 Kb.
  1   2   3

D&C FJS/AS:dja DEPARTMENT OF CORRECTIONAL SERVICES

SECTION 283101
PROTECTED PREMISES FIRE ALARM SYSTEM

THIS SECTION SHOULD BE USED FOR DEPARTMENT OF CORRECTIONAL SERVICES PROJECTS.
THIS SECTION COVERS A SYSTEM WHICH HAS ONE OR MORE MICROPROCESSOR BASED FIRE ALARM CONTROL PANELS IN EACH BUILDING, WHICH HAVE FIRE ALARM, CONTROL, AND REAL TIME CAPABILITIES. INITIATING AND CONTROL DEVICES ARE HARD WIRED OR MULTIPLEXED TO THE FACP(S). WHERE MULTIPLE FACP’S ARE USED, THEY ARE MULTIPLEXED TO EACH OTHER. EACH BUILDING FIRE ALARM SYSTEM IS MONITORED BY THE FACILITY MONITORING AND CONTROL MULTIPLEX SYSTEM (SECTION 281603).
IN ADDITION TO THE NEW YORK STATE UNIFORM FIRE PROTECTION AND BUILDING CODE (NYSUFP&BC), THIS SECTION WAS WRITTEN TO MEET:

1. FOR THE BUILDING: NFPA 72 CHAPTER 3 PROTECTED PREMISES FIRE ALARM SYSTEMS.

2. THE ESSENCE OF ALL THE ADDITIONAL CODES, STANDARDS AND REFERENCES LISTED UNDER INFORMATION AT END OF SECTION. HOWEVER, YOU MUST EVALUATE THE CODES AND STANDARDS FOR REQUIREMENTS WHICH ARE RELEVANT TO ONLY SPECIFIC APPLICATIONS SUCH AS HEALTH AND MENTAL CARE FACILITIES, INDUSTRIAL BUILDINGS, STORAGE FACILITIES, HAZARDOUS AREAS, NYC PROJECTS, ETC. AND MODIFY THIS SECTION TO ACCOMMODATE THEIR SPECIAL REQUIREMENTS.
SEE INFORMATION AT END OF SECTION.
PART 1 GENERAL
1.01 RELATED WORK SPECIFIED ELSEWHERE
A. Video Training Programs: Section 0117900.
B. Main Security Console: Section 281601
INSERT APPROPRIATE SECTION NUMBER IN PARAGRAPH BELOW.

C. Facility Monitoring and Control Multiplex System: Section .


1.02 REFERENCES
A. Underwriters Laboratories Inc.
IN PARAGRAPH BELOW ADD “and 13” FOR SPRINKLER SYSTEM ALARM AND SUPERVISION. ADD “and 20” FOR FIRE PUMP SUPERVISION.

B. National Fire Protection Association Standard 72.


1.03 DEFINITIONS
A. Initiating Device Circuit: A circuit to which automatic or manual initiating devices are connected where the signal received does not identify the individual device operated. Example:

1. Circuits from FACP to non-addressable signal initiating devices.


B. Notification Appliance Circuit: A circuit or path directly connected to a notification appliance. Example:

1. Circuits from FACP to notification appliances.


C. Signaling Line Circuit: A circuit or path between any combination of circuit interfaces, control units, or transmitters over which multiple system input signals or output signals, or both are carried. Examples:

OMIT SUBPARAGRAPH BELOW IF ONLY ONE FACP IS USED.

1. Circuits between FACP’s.

2. Circuits from FACP to addressable devices.
D. Operating Mode:

1. Private Mode:

a. Audible and visible signaling only to those persons directly concerned with the implementation and direction of emergency action initiation and procedure in the area protected by the fire alarm system, and:

b. Audible and visible signaling only to those persons within special designated areas where private mode operation is specified to be applicable.

2. Public Mode: Audible and visible signaling to occupants or inhabitants of the area protected by the fire alarm system.
1.04 SYSTEM DESCRIPTION

FOR SINGLE PANEL PROJECT, OMIT REFERENCE TO ICU’s THROUGHOUT SYSTEM DESCRIPTION (MFACP TERMINOLOGY IS APPLICABLE TO A SINGLE PANEL OR MULTIPLE PANEL BUILDING).
INSERT APPROPRIATE SECTION NUMBER IN PARAGRAPH BELOW.

A. The Facility Monitoring and Control Multiplex System (FMCMS), Section , monitors and controls each Protected Premises Fire Alarm System, and equipment located throughout the facility.


B. Each building system operates as a multiplexed protected premises fire alarm/emergency communication monitoring and control system.

USE FIVE SUBPARAGRAPHS BELOW FOR MULTI-PANEL BUILDINGS.

1. In Buildings With More Than One Fire Alarm Control Panel: Changes in the status of monitored points are indicated at the microprocessor based main fire alarm control panel (MFACP), utilizing distributed processing, peer-to-peer networked, interconnected control unit’s (ICU’s) located throughout the building.



SHOW EMERGENCY LIGHTING AT MFACP. SHOW A SMOKE DETECTING DEVICE IN EACH AREA WHERE FIRE ALARM PANELS ARE INSTALLED (NFPA 72 1-5.6).

a. The network micro-processors continually monitor the communications and data processing cycles of the building system.

1) A communications failure indication (print-out, display and audible alarm) occurs at the MFACP upon failure of the network communication and data processing cycle.

b. Upon MFACP failure, an audible and visible alarm activates.

1) Complete failure of the MFACP does not interfere with the ability of each ICU to perform its functions.

USE TWO SUBPARAGRAPH BELOW FOR SINGLE PANEL BUILDINGS.

2. In Buildings With One Fire Alarm Control Panel: Changes in the status of monitored points are indicated at the microprocessor based main fire alarm control panel (MFACP).

a. The MFACP continually monitors the communications and data processing cycles of the microprocessor. Upon MFACP failure, an audible and visible alarm activates at the MFACP.

3. Upon MFACP failure a building (common) trouble condition is also indicated at the FMCMS.

4. Smoke detectors and smoke sensors operate in conjunction with the systems’ alarm verification program.

IN AREAS WHERE ALARM VERIFICATION FEATURE IS DESIRED FOR ADDITIONAL PROTECTION AGAINST FALSE ALARMS OR UNWARRANTED DISCHARGE OF FIRE SUPPRESSION SYSTEMS, ALARM VERIFICATION ZONES FOR SMOKE DETECTORS, OR INDIVIDUAL SMOKE SENSORS OPERATING IN VERIFICATION MODE MUST BE INDICATED ON THE DRAWINGS. REFER TO NFPA 72 3-8.3.2.3.1.

a. The alarm verification operation is selectable by zone for smoke detectors and by individual devices for smoke sensors.

b. The activation of any smoke detector within its zone initiates the alarm verification program.

1) The panel resets the activated detector and waits for a second alarm activation. If within one minute a second alarm is reported from any detector within the zone, the system alarms. If no second alarm within one minute, the system resumes normal operation.

c. The system can display the number of times (tally) a smoke detector zone or smoke sensor has gone into a verification mode. A trouble condition occurs when the tally reaches a pre-programmed number.

5. Smoke sensors act as intelligent and addressable devices. The smoke sensor converts the condition of it’s smoke sensing chamber to an analog value. This analog value is digitized and transmitted to the FACP(s).

a. Actual smoke density and temperature measurements are referenced from average sample measurements and are compared to programmable values of threshold sensitivity.

b. Sensor “dirty” and “excessively dirty” trouble conditions are reported automatically through a maintenance advisory and alert program procedure.

c. The system continuously performs an automatic self-test routine on each sensor which checks sensor electronics to ensure the accuracy of the values being transmitted to the FACP(s). Sensors that fail are identified and indicate a trouble condition.

d. System automatically performs NFPA 72 sensor sensitivity testing by:

1) Frequent routine individual sensor alarm simulation testing.

2) Trouble signal when sensor is outside its acceptable sensitivity range.

6. System individually identifies each addressable initiating device and other addressable monitor functions using multiplexing techniques.

7. System is capable of individually operating each alarm notification appliance, and other control functions, using multiplexing techniques.

8. Alarms are processed by the system at 3 levels of priority:

a. Fire alarms, supervisory, and trouble signals take precedence in that respective order of priority, over all other signals.

b. Other alarms that require interaction by the attendant have the second level of priority.

c. Monitored points which do not require interaction by the attendant are the third level of priority.

9. Alarms, supervisory signals, and trouble signals are distinctively and descriptively annunciated.

a. Fire alarm signals are distinctive in sound from other signals, and this sound is not used for any other purpose.

b. Supervisory signals are distinctive in sound from other signals.

1) System differentiates between supervisory device activation and trouble (wiring faults) on independent supervisory service initiating circuits.

c. Trouble signals are indicated by distinctive audible signals. Exception: The same sound may be used for both supervisory signal and trouble signal if distinction is made between signals by visible annunciation.

10. Switches for silencing audible trouble and supervisory signals transfers the audible signal to an identified lamp or other visible indicator adjacent to the switches. The visible indication persists until the condition has been corrected. The audible signal sounds when the switch is in its silence position and no trouble or supervisory condition exists.

a. Trouble silencing switch does not prevent sounding of supervisory signal. Subsequent supervisory signals from other zones causes the supervisory signal to resound. A switch left in the silence position where there is no supervisory off-normal signal operates a visible signal silence indicator and causes the trouble signal to sound until the switch is returned to normal.

b. A silenced audible trouble signal resounds at programmable time intervals (every 24 hours or less) as a reminder that the trouble condition has not been corrected. Re-sounded signal is retransmitted to all locations required of the original trouble signal.

11. System visible and audible trouble signals and supervisory signals and visible indication of their restoration is indicated at the MFACP.

OMIT SUBPARAGRAPH BELOW IF NOT APPLICABLE.

a. Each ICU’s visible and audible trouble signals and visible indication of their restoration is indicated at the ICU.

b. Monitoring of ground fault conditions indicate a ground fault trouble condition at the MFACP.

c. Ground fault trouble condition also indicates building (common) trouble condition at the FMCMS.

12. Trouble conditions are sent to the FMCMS via transponders located in the FMCMS Equipment Cabinet (FEC).

a. Each building MFACP transmits one (common) system trouble condition to the FMCMS. Facility personnel will check the building’s MFACP to determine the specific system trouble condition(s) within the building.

13. Access to the system functions are controlled thru at least 3 levels of access security to prevent program modifications or use by unauthorized personnel:

a. At the lowest level of access the system automatically receives, displays and prints alarms, and performs control-by-event life safety functions. The attendant has minimum access to the system functions:

1) Alarm acknowledge.

2) Silence alarms.

3) Perform other basic system functions that require interaction by the attendant (cannot change program parameters).

b. At mid-level of access, the attendant may change user programmable parameters and print all summaries.

c. At the highest level of access, programs may be modified by the system manager (life safety control-by-event programs may be field or factory modified).

d. System access functions (log on, log off, access level authority) are displayed with date, time, and persons name.

14. Summary reports are displayed at the MFACP upon appropriate function command. Active control points are identified by an assigned message. Spare control points are identified by a point number. The summary reports can be interrupted and terminated and the system returned to normal operation by a manual reset control or automatically if the system senses a change of status signal. The summary reports include:

a. Current Alarm, Trouble, and Supervisory Conditions: Lists all points not in normal state.

b. Alarm historical log report.

c. Trouble and supervisory historical log report.

d. All Points: Lists every point in the system and current status of the point.

e. Control by Event Programs: Lists data for event initiated programs.

f. Control by Time Programs: Lists data for time initiated programs.

g. Diagnostics:

1) Alarm verification cycles initiated by a smoke detector zone or individual smoke sensors.

2) Smoke sensor service report: Device number, device type, custom label, presently selected alarm set point information, present average value, present value, peak observed values, service status.

3) Smoke sensor status report: Device number, device type, custom label, present sensitivity in % for smoke sensors and in degrees for temperature sensors, present status, and sensor range (normal, almost dirty, dirty).

4) Devices which fail automatic tests.

5) Walk test reports.

15. Life safety control-by-event functions are retained in a non-volatile programmable memory and are not alterable through normal operation of the system.

a. The life safety control-by-event control points may be manually operated at any time by authorized personnel thru appropriate system commands.

16. User programmable control-by-event functions may be programmed thru appropriate system commands to automatically activate any user programmable control point upon a status change from any programmable monitor point.

a. The user programmable control-by-event control points may be manually operated at any time by the attendant thru appropriate system commands.

17. User programmable parameters for automatic time-initiated functions (start/stop, on/off, secure/access, etc.) may be added, omitted and altered thru appropriate system commands.

a. The time-initiated user programmable control points may be manually operated at any time by authorized personnel thru appropriate system commands.

OMIT WALK TEST SUBPARAGRAPHS BELOW FOR SMALL SYSTEM (ALSO OMIT REFERENCE TO WALK TEST FROM PREVIOUS SUMMARY REPORTS SUBPARAGRAPH).

18. One person may test the system (walk test).

a. When in testing mode:

1) Alarm activation of an initiating device circuit is silently logged as an alarm condition in the historical data file. The system automatically resets after logging each alarm.

2) The momentary disconnection of an initiating device or notification appliance circuit is silently logged as a trouble condition in the historical data file. The system automatically resets after logging each trouble condition.

3) The person testing the system may also choose to have the system activate the alarm notification appliances for a maximum of two seconds upon initiating device testing and a maximum of four seconds upon trouble condition testing.

4) If in the test mode for an inappropriate (programmable) amount of time, the system automatically reverts to normal mode.

5) The municipal or remote station connection is bypassed.

6) The system shows a trouble condition.

7) Control relay functions are bypassed.

b. Testing groups allow portions of the system to be placed in test mode while the non-test groups remain in normal mode.
C. The MFACP activates immediately and performs its alarm functions upon receipt of system alarm condition thru actuation of automatic or manual initiating devices:

1. The MFACP sounds its audible alarm and illuminates its system alarm lamp or flashing display.

a. The audible alarm pulses until the system acknowledge button is depressed.

b. The system alarm lamp remains illuminated until the alarm condition has been corrected and the system reset.



REFER TO NFPA 72 1-5.7.3 AND NFPA 101 9.6.7 FOR ALARM ANNUNCIATION REQUIREMENTS.

2. The MFACP displays the point and type of alarm condition. Addressable devices are individually identified. Groups of non-addressable devices are identified by zones.

3. Upon receipt of an alarm condition through activation of a manual initiating device, a manually operated device alarm condition is sent to the FMCMS via transponders located in the FMCMS Equipment Cabinet (FEC).

4. Upon receipt of an alarm condition through activation of an automatic initiating device, an automatically operated device alarm condition is sent to the FMCMS via transponders located in the FEC.

5. An authorized person at the MFACP presses the acknowledge button which silences its audible alarm and causes a display of the assigned message for the point in alarm with date, time and an acknowledge prefix.

SUBPARAGRAPH BELOW IS REQUIRED BY NYSUFP&BC 1060.2( a)(4) FOR C6.3 OCCUPANCY. INDICATE WHERE SIGN AND VISIBLE SIGNAL IS TO BE LOCATED ON THE PREMISES IN A CONSPICUOUS LOCATION.

6. A remote annunciator and procedure sign located at ________ instructs personnel on procedure to be followed in the event of a fire.

a. Visible signal illuminates drawing attention to the procedure sign.

IF A POSITIVE ALARM SEQUENCE ALARM OR A PRESIGNAL FEATURE IS PREFERRED, MODIFY LIFE SAFETY CONTROL-BY-EVENT FUNCTIONS BELOW TO SUIT OPERATION. REFER TO NFPA 72 1-5.4.11, NFPA 101 9.6.3.3 & 9.6.3.4, AND NYSUFP&BC 1060.2( a)(6). THERE ARE MANY OCCUPANCIES LISTED IN NFPA 101 WHERE EITHER POSITIVE ALARM SEQUENCE OR PRESIGNAL OR BOTH ARE PROHIBITED.
IN SUBPARAGRAPH BELOW OMIT ICU’s IF NOT APPLICABLE.
SHOW WHERE AUDIBLE NOTIFICATION APPLIANCES ARE REQUIRED. REFER TO NFPA 72 CHAPTER 4, NYSUFP&BC 1060.2( C), AND ANSI A117.1. SHOW SUFFICIENT NUMBER OF AUDIBLE APPLIANCES SO THAT, WHEN TESTED, THE SYSTEM WILL MEET THE SPECIFIED PRIVATE AND PUBLIC MODE SOUND LEVEL PARAMETERS.
SHOW NOTIFICATION APPLIANCE WIRING RUN TO AN MFACP FROM EACH AREA

WHERE ALARM IS TO BE SOUNDED (FLOOR BY FLOOR, AREA BY AREA, ETC). COORDINATE WIRING WITH FUNCTION SPECIFIED. REFER TO NFPA 72 3-8.4.1.1 AND 3-8.4.1.3.6.
D. Life Safety Control-By-Event Functions: The MFACP and ICU’s immediately performs life safety control-by-event functions upon system alarm condition:

INDICATE WHERE REMOTE ANNUNCIATORS ARE REQUIRED. REFER TO NYSUFP&BC 791.2, 1060.2(4) & (5).

1. Remote annunciators are activated in each ________ and mechanical equipment room, drawing attention to the alarm condition.

2. All Buildings (unless otherwise specified): Private and public mode audible alarm notification appliances within the building in which the alarm condition is initiated sounds a continuous alarm signal throughout the building.

3. Housing Buildings and Medical Buildings: Audible alarm notification appliances within the building in which the alarm condition is initiated do not automatically sound upon receipt of an alarm condition thru actuation of an automatic initiating device. A buzzer sounds and visible indicators illuminate in each remote annunciator in the building in which the alarm condition is initiated. Visible indicator labels state “Fire-Automatic Devices”. A switch at the remote annunciator allows silencing the buzzer, but visual indicators remain illuminated until the system is reset.

a. Each remote annunciator contains the indicators listed above for all floors in the building.

b. All private and public mode audible alarm notification appliances (all bells throughout the building) are controlled by selector switches located in a separate surface mounted enclosure (RA/CC) adjacent to the MFACP. A selector switch (on, off) for each zone controls the bells in that zone. In the “Off” position the notification appliances within the building or floor will not sound (no trouble indication for the notification appliances). In the “On” position the notification appliances within the building or floor sound, and an alarm condition is sent to the MFACP indicating actuation of a manual initiating device.

4. Private mode audible signals have a sound level of not less than 45 dBA at 10 Feet, nor more than 120 dBA at the minimum hearing distance from the audible appliance. Also, the audible signal has a sound level at least 10 dBA above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5 feet above the floor in the occupiable area.

a. Unless otherwise indicated, 45 dBA private mode audible signals sound in:



EDIT LIST BELOW. WHERE OCCUPANTS ARE INCAPABLE OF EVACUATING THEMSELVES BECAUSE OF AGE, PHYSICAL OR MENTAL DISABILITIES, OR PHYSICAL RESTRAINT, ALSO USE THE 45 dBA PRIVATE MODE. SPECIFY THE AREAS. REFER TO NFPA 72 4-3.3, NFPA 101 9.6.3.6 & 9.6.3.7 AND UL 464.3.2.

1) Security office.

2) Elevator cars.

3) Public restrooms.

4) Patient sleeping areas.

REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 72 4-3.1.4, 4-3.3.2 & APPENDIX A4-3.3.2.

5. Private mode audible signals in mechanical equipment rooms have a sound level of not less than 100 dBA at 10 feet, nor more than 120 dBA at the minimum hearing distance from the audible appliance. Also, the audible signal has a sound level at least 10 dBA above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5 feet above the floor.

6. Public mode audible alarm signals have a sound level of not less than 75 dBA at 10 feet nor more than 120 dBA at the minimum hearing distance from the audible appliance. Also, the audible signal has a sound level at least 15 dBA above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds (whichever is greater) measured 5 feet above the floor in each occupiable area.

7. The system allows an authorized person to:

a. Silence any alarm signal in progress through a silence command, but subsequent actuation of initiating devices on other initiating device circuits or subsequent actuation of addressable initiating devices on signaling line circuits causes the system to resound the alarm.

1) Silencing of an audible alarm does not cancel any visible zone alarm indicators.

2) A silencing means that it is left in the “off” position when there is no alarm operates an audible trouble signal until the means is restored to normal.

MODIFY SUBPARAGRAPH BELOW TO SUIT BUILDING LAYOUT.

b. Activate the alarm notification appliances on selected floors, and all floors.

1) Visible indicators in the RA/CC at the MFACP indicate on/off status of the alarm notification appliances.

REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 101 9.6.3.2.

8. Alarm signal does not sound in stairwells or elevators.

9. Actuation of smoke detecting devices in stairwells, or elevator shafts do not sound the alarm signal, but activates all other system alarm functions.

SHOW WHERE VISUAL NOTIFICATION APPLIANCES ARE REQUIRED. REFER TO NFPA 72 CHAPTER 4, NYSUFP&BC 1060.2(A)(7), AND ANSI A117.1 CHAPTER 7. DO NOT SHOW VISUAL ALARMS AND AUDIBLE ALARMS CONNECTED ON THE SAME CIRCUITS.
REFER TO NFPA 72 4-4 FOR PUBLIC MODE VISIBLE CHARACTERISTICS AND NFPA 72 4-5 FOR PRIVATE MODE VISIBLE CHARACTERISTICS.

10. Public and private mode visible alarm notification appliances illuminate and flash a fire warning signal.

a. All Buildings (unless otherwise specified): Visible notification appliances illuminate and flash a fire warning signal within the building in which the alarm condition is initiated.

b. Housing Buildings and Medical Buildings: Visible notification appliances within the building in which the alarm condition is initiated do not automatically illuminate and flash a fire warning signal upon receipt of an alarm condition thru actuation of an automatic initiating device.

1) Selector switch control for activation of the audible alarm notification appliances also causes activation of the visible notification appliances so that they illuminate and flash a fire warning signal within the activated audible alarm notification zone(s).

c. Public mode visible signaling flash rate does not exceed 2 flashes per second, nor less than one flash every second throughout the listed voltage range of the appliance.

1) The maximum pulse duration is 0.2 seconds with a maximum duty cycle of 40 percent. The pulse duration is defined as the time interval between initial and final points of 10 percent of maximum signal.

2) The light source is clear or nominal white and does not exceed 1000 candela (effective intensity).

d. All strobes are synchronized to flash simultaneously to reduce the probability of photo-sensitive reactions.

e. Visible alarms continue to flash until the initiating devices are restored to normal condition and the system is manually reset.



REFERENCES FOR SUBPARAGRAPH BELOW ARE NFPA 72 2-10.6, 3-9.6, NYSUFP&BC 1060.9 & NFPA 101 7.2.1.8.2, 7.2.1.9.2, 7.2.13.5, 9.6.5.2.

11. Electromagnetic door hold-open devices de-energize, allowing the associated smoke doors to close.



INCLUDE SUBPARAGRAPH BELOW IF FIRE HOSE CABINET DOORS ARE LOCKED IN GROUP C6.3 OCCUPANCY. REFER TO NYSUFP&BC 1060.5( a)(5).

12. Fire hose cabinet doors unlock.



COORDINATE SUBPARAGRAPH BELOW WITH HARDWARE DESIGNERS. REFER TO NFPA 72 3-9.7 & NFPA 101 7.2.1.5, 7.2.1.6, 9.6.5.2.

13. Locked doors for re-entry from exit stairwells, exit doors, and emergency exits release their fail safe door lock mechanisms so that associated doors may be opened.



IF ANY OF THE NEXT SEVERAL SUBPARAGRAPHS APPLICABLE TO SMOKE/FIRE CONTROL ARE USED, REFER TO NFPA 72 3-9.5, NFPA 90, 92A, NFPA 101 9.6.5.2, AND NYSUFP&BC 1004.2(e)(2), (3) & (4), 1004.2(f)(2). COORDINATE WITH HVAC. THEY MAY INCLUDE A SMOKE/FIRE CONTROL SYSTEM IN THEIR CONTRACT. SPECIFY THE FUNCTIONS THAT THE AUTOMATED BUILDING HVAC SYSTEM WILL CONTROL UPON SIGNAL FROM THE FIRE ALARM SYSTEM.

14. Selected HVAC equipment (ventilating fans, air handling units, (_______) shut down.



COORDINATE SUBPARAGRAPH BELOW. IN A SPRINKLERED BUILDING FIRE ALARM ZONES MAY ALSO BE SAME AS SPRINKLER ZONES.

a. Fire alarm zones are coordinated with the smoke control zones that they actuate.



REFERENCE FOR SUBPARAGRAPH ABOVE AND BELOW IS NFPA 72 3-9.5.4.
INCLUDE SUBPARAGRAPH BELOW IF THERE IS A CONNECTION TO A DDC SYSTEM AND EDIT TO SUIT OPERATION. REFER TO NFPA 72 3-9.2.5.

1) Fire alarm zone(s) activated by fire alarm system automatic or manual initiating devices (including sprinkler waterflow switch) causes HVAC equipment to shut down (or perform other required program operation) within the alarmed fire alarm zone(s) thru connection (network or other digital communication technique) to the direct digital building control system.



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 72 3-9.5.3, NFPA 90A 4-4.4.2, AND NFPA 101 9.6.3.2.

b. Actuation of air duct smoke detecting devices used solely for HVAC system shutdown does not sound the alarm signal but activates all other MFACP alarm functions.



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 90A 4-2.

c. Each air distribution system supply, return, and exhaust fan can be manually stopped by the attendant at the MFACP during an emergency.



REFERENCE FOR SUBPARAGRAPH BELOW IS NYSUFP&BC 1004.0(e)(4). SHOW LOCATION OF SWITCH.

d. An emergency switch for each system ventilating an assembly space is located to enable manual shut down of the system in case of fire or smoke. A sign located adjacent to the switch states instructions for system shut down.



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 90A 4-4.2 & 4-4.3.

15. Smoke detectors listed for use in air distribution systems and located as indicated below, automatically stop their respective fan(s) on detecting the presence of smoke:

a. Downstream of the air filters and ahead of any branch connections in air supply systems having a capacity greater than 2000 ft.³/min.

b. At each story prior to the connection to a common return and prior to any recirculation or fresh air inlet connection in air return systems having a capacity greater than 15, 000 ft.³ /min. and serving more than one story.



REFERENCE FOR SUBPARAGRAPH BELOW IS NYSUFP&BC 1004.2(e)(2).

16. Safety controls operate for every system using recirculated air and serving an area of public assembly or more than one fire area, or more than one story of a building:

a. When the air in the system contains smoke of predetermined intensity or has an abnormal rise in temperature, the fans causing normal circulation in such area stops and requires manual reset at the fire alarm control panel.

REFERENCE FOR SUBPARAGRAPH BELOW IS NYSUFP&BC 1004.2(e)(5).

17. Automatic devices for systems ventilating high hazard spaces stop the fans when the air in the system contains smoke of a pre-determined quantity or has an abnormal rise in temperature. Controls require manual reset.



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 101 8.3.5.2 & 8.3.5.3.

18. Fire dampers and smoke dampers close.

a. Actuation of air duct smoke detecting devices used solely for the closing of dampers does not sound the alarm signal but activates all other MFACP alarm functions.

REFERENCE FOR THREE SUBPARAGRAPHS BELOW IS NFPA 90A 4-3.

b. Attendant at the MFACP may manually position the smoke dampers.

c. Smoke dampers, which isolate the air-handling system, close automatically when the system is not in operation.

d. Smoke dampers installed in smoke barriers may remain open during fan shutdown provided that their associated controlling damper actuators and smoke detecting devices remain operational. Dampers close automatically when the fan system they are serving is not in operation.



REFERENCES FOR SUBPARAGRAPH BELOW ARE NFPA 70 645-10 AND NFPA 75 8-1.1.

e. Dampers in HVAC systems serving computer areas and automatic fire and smoke dampers installed where ducts pass through fire-resistant-rated construction operate upon activation of smoke detecting devices and by operation of the computer room disconnecting means for all electronic equipment, dedicated HVAC systems servicing the computer room, and uninterruptible power supplies.


1. SHOW SMOKE DETECTING DEVICE SPECIFICALLY ASSOCIATED WITH THE OPERATION OF EACH ROLLING FIRE SHUTTER AND FIRE DOOR. REFER TO NFPA 80 1-10, 6-4.1, 6-4.2, & nfpa 101 9.6.5.2.

2. SHOW EMERGENCY RELEASING DEVICE CONTROL PANEL (BY OTHERS) ASSOCIATED WITH EACH ROLLING FIRE SHUTTER AND DOOR WHICH IS CONNECTED TO THE FIRE ALARM SYSTEM.

3. SHOW 120VAC CIRCUIT CONNECTED TO RELEASING DEVICE CONTROL PANEL IN ADDITION TO POWER CIRCUIT REQUIRED FOR MOTOR OPERATOR IF SO EQUIPPED (ADDITIONAL 120VAC CIRCUIT MAY NOT BE REQUIRED IN ALL CASES FOR MOTORIZED SYSTEMS DEPENDING ON MOTOR HORSEPOWER AND TYPE OF OPERATOR).

4. SHOW WIRING FROM FIRE ALARM PANEL TO RELEASING DEVICE CONTROL PANEL. FIRE ALARM SYSTEM CAN ONLY ACTUATE CLOSING. THERE IS NO PROVISION AVAILABLE WITHIN THE RELEASING DEVICE CONTROL PANEL TO HAVE THE FIRE ALARM SYSTEM MONITOR THE BATTERY OR ANY OTHER TROUBLE CONDITIONS. THERE IS A FORM C CONTRACT AVAILABLE THAT COULD BE CONNECTED TO THE FIRE ALARM SYSTEM SHOWING THAT THE RELEASING DEVICE CONTROL PANEL HAS OPERATED.

5. VERIFY THAT THE SPECIFICATION FOR THE EMERGENCY RELEASING DEVICE CONTROL PANEL IN SECTION 083323 ENCOMPASSES THE OPERATION SPECIFIED IN SUBPARAGRAPHS BELOW.

19. Non-motorized rolling fire shutters and fire doors close when the associated smoke detecting devices are actuated. The fire alarm system initiates closure through the fire door’s emergency releasing device control panel:

a. There is a ten second delay before door releases.

b. An audible and visible warning occurs during the time delay and during closing cycle that the door is closing.

c. The releasing device control panel independently performs other safety and operational functions associated with fire door closing during alarm condition.

20. Motorized rolling fire shutters and fire doors close when the associated smoke detecting devices are actuated. The fire alarm system initiates closure through the fire door’s emergency releasing device control panel:

a. For doors which require mechanical resetting after release:

1) There is a ten second delay before door releases.

2) An audible and visible warning occurs during the time delay and during closing cycle that the door is closing.

3) Electric operator closes the door with motor power upon alarm, when power is available to the motor operator.

4) When power is not available to the motor operator during alarm condition, the ten second delay and warnings are initiated before door releases.

5) The releasing device control panel independently performs other safety and operational functions associated with fire door closing during alarm condition.

b. For door which do not require mechanical setting:

1) Electric operator closes the door with motor power upon alarm, when power is available to the motor operator.

2) When power is not available to the motor operator (alarm condition or no alarm condition) the door closes by gravity as soon as power fails.

3) The releasing device control panel independently performs other safety and operational functions associated with fire door closing during alarm condition.



FOR NEXT TWO SUBPARAGRAPHS REFER TO NYSUFP&BC 739.4(d)(8), 771.4(h)(10) AND 1060.9.
1. SHOW SMOKE DETECTING DEVICE SPECIFICALLY ASSOCIATED WITH THE OPERATION OF EACH ROOF VENT.

2. SHOW WIRING TO EACH ROOF VENT EMERGENCY ELECTRIC RELEASE DEVICE.

3. SHOW WIRING TO EACH ROOF VENT “OPEN” SWITCH.

21. Heat and smoke roof vents open when the associated smoke detecting devices are actuated. Visible indicators in the RA/CC’s illuminate, indicating which roof vents are open.



CHECK WITH ELEVATOR DESIGNERS FOR DETAILS ON HOISTWAY VENTING. MODIFY SUBPARAGRAPH BELOW TO SUIT. REFER TO NFPA 3-9.3.4 EXCEPTION NO. 2.

22. Elevator hoistway heat and smoke vents open when the associated smoke detecting devices are actuated. Visible indicators in the RA/CC’s illuminate, indicating which vents are open.



FOR THE NEXT SEVERAL SUBPARAGRAPHS PERTAINING TO ELEVATOR EMERGENCY RECALL OPERATION, REFER TO NFPA 72 3-9.3, ANSI/ASME A17.1, AND NFPA 101 7.2.12.2.4 & 9.4.3. COORDINATE WITH ELEVATOR DESIGNERS.
FOR ELEVATOR RECALL FOR FIRE FIGHTERS’ SERVICE, NFPA 72 3-9.3.4 STATES THAT “SMOKE DETECTORS SHALL NOT BE INSTALLED IN ELEVATOR HOISTWAYS” (WITH 2 EXCEPTIONS). IN SUBPARAGRAPHS BELOW REMOVE THE WORD “HOISTWAY” UNLESS IT COMPLIES WITH EXCEPTION NO. 1 (WHERE THE TOP OF THE ELEVATOR HOISTWAY IS PROTECTED BY AUTOMATIC SPRINKLERS), OR EXCEPTION NO. 2 (WHERE A SMOKE DETECTOR IS INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY SMOKE RELIEF EQUIPMENT).

23. Phase I automatic elevator recall for fire fighter’s service operates upon actuation of an elevator lobby smoke detecting device (excluding the designated floor lobby smoke detecting device) or actuation of an associated hoistway or machine room smoke detecting device. All elevators that service that lobby return non-stop to the designated floor. (If the smoke detecting device at the designated floor is activated, the elevators that serve that level return non-stop to the alternate floor).

a. Each elevator lobby, hoistway and machine room smoke detecting device is capable of initiating elevator recall when all other devices on the same initiating device circuit have been manually or automatically placed in the alarm condition.

b. The elevator automatic (smoke detecting devices) and manual (two and three position key switches) Phase I Emergency Recall Operation and the Phase II Emergency In-Car Operation operate in accordance with the applicable ANSI/ASME A17.1 Rules 211.3 thru 211.8 and NFPA 72 3-9.3.

c. For each group of elevators, three separate elevator control circuits terminate at the designated elevator controller within the group’s elevator machine room.

d. The smoke detecting devices actuate the three elevator control circuits as follows:

1) The smoke detecting devices located in the designated elevator recall lobby actuates the first elevator control circuit. In addition, where the elevator is equipped with front and rear doors, the smoke detecting devices in both lobbies at the designated level actuate the first elevator control circuit.

a) The first control circuit prevents recalling the elevators and discharging passengers to the designated floor when the designated floor is the fire location, and to provide for an alternate recall location when the designated floor is reporting a fire condition;

2) The smoke detecting devices in the remaining elevator lobbies actuate the second elevator control circuit.

a) The second control circuit provides standard recall to the designated floor when any other elevator lobby, machine room or hoistway smoke detecting device is in alarm;

3) The smoke detecting devices in elevator hoistways and the elevator machine room(s) actuate the third elevator control circuit. In addition, where the elevator machine room is located at the designated level, that elevator machine room smoke detecting device also actuates the first elevator control circuit.

a) The third control circuit is for the safety of the fire fighters who may be using the elevators to bring equipment to staging areas. This circuit also overrides the fire fighter’s key operation and brings the elevators to a safe level of discharge prior to equipment shutdown due to fire in hoistway or machine room. The circuit also sounds a warning in the elevator cab notifying the fire fighters using the elevator to immediately move to a safe floor and exit the elevators;



TWO SUBPARAGRAPHS BELOW ARE REQUIRED BY NFPA 72 3.9.3.6. OMIT THE WORD “HOISTWAY” IN THE NEXT 2 SUBPARAGRAPHS UNLESS IT COMPLIES WITH NFPA 72 3-9.3.4.

24. Each elevator lobby, hoistway, and machine room smoke detecting device, when actuated, initiates a system alarm condition. The alarmed zone, or addressable device is visibly annunciated at the MFACP and the ICU’s associated with the elevators.

a. Additionally, the hoistway and machine room smoke detecting devices visibly annunciate at the MFACP and ICU’s separately and distinctly from other visible annunciation, to alert fire fighters and other emergency personnel that the elevators are no longer safe to use due to smoke and fire intrusion into the hoistways and machine rooms.

CHECK WITH ELEVATOR DESIGNERS FOR DETAILS OF ELEVATOR SHUTDOWN. SHOW DESIGN ON DRAWINGS. TYPE OF HEAT DETECTING DEVICE USED MUST BE COORDINATED WITH SPRINKLER HEADS TO ENSURE THAT HEAT DETECTING DEVICE WILL RESPOND BEFORE THE SPRINKLER HEADS. REFER TO ANSI A17.1, RULE 102.2 AND NFPA 72 3-9.4.

25. Elevator Shutdown Prior to Sprinkler Operation:



THE FOLLOWING SUBPARAGRAPHS SPECIFY ONE METHOD OF ACCOMPLISHING ELEVATOR SHUTDOWN. OTHER METHODS INCLUDE (CHECK WITH SPRINKLER DESIGNER FOR APPROPRIATE METHOD):

1. USE HEAT DETECTOR TO SHUNT TRIP THE CIRCUIT BREAKER. A SECOND SET OF CONTACTS IN THE HEAT DETECTOR IS USED TO MONITOR THE ALARM. REMOTE ADDRESSABLE NETWORK MODULES MONITOR POWER TO SHUNT TRIP CIRCUIT.

2. HEAT DETECTOR OPERATES SOLENOID VALVE TO ALLOW WATER TO FLOW INTO THE SYSTEM. THIS METHOD USUALLY OPERATES THROUGH A CONTROL PANEL FOR MONITORING, ALARM AND TRIPPING FUNCTIONS.

a. Dedicated elevator shutdown ICU’s located in each elevator machine room, in conjunction with heat detecting devices located within two feet of each sprinkler head monitors the hoistways and machine rooms for heat/fire conditions.

1) The heat detecting device has both a lower temperature rating and a higher sensitivity as compared to the sprinkler, to ensure heat detecting device response prior to sprinkler head operation.

2) The elevator shutdown ICU’s and heat detecting devices are independent of the sprinkler system.

b. Smoke detecting devices located in each hoistway and elevator machine room monitor the hoistways and machine rooms for smoke/fire conditions. The smoke detecting devices are connected to system ICU’s. The smoke detecting devices are not connected to the elevator shutdown ICU’s. Sequence of Events:

1) Smoke in a machine room or hoistway during the initial stages of a fire activate the system smoke detecting devices, causing the system to perform the elevator recall functions.

2) As the intensity of the fire builds, the elevator shutdown heat detecting devices actuate, causing the elevator shutdown ICU to shunt trip the circuit breaker serving the main power line to affected elevators prior to the application of water. The sprinkler system operates independently after the affected elevator has shutdown.

3) Activation of elevator machine room or hoistway heat detecting devices are indicated by an audible alarm and a visual indicator in the MFACP.



FOR SUBPARAGRAPH BELOW, REFER TO NFPA 72 3-9.4.4. AND APPENDIX A3-9.4.1.4. FOR DIAGRAM SHOWING TYPICAL METHOD OF PROVIDING ELEVATOR POWER SHUNT TRIP SUPERVISORY SIGNAL.

c. Control circuits to shut down elevator power are monitored for presence of operating voltage. Loss of power to the control circuit for the disconnecting means causes a supervisory signal to be indicated at the ICU and MFACP. Refer to NFPA 72 A-3.9.4.4 for a typical method of providing elevator power shunt trip supervisory signal.



SUBPARAGRAPH BELOW IS REQUIRED UNDER CERTAIN CONDITIONS BY NFPA 101 9.4.5.

26. Elevator machine rooms that contain solid-state equipment for elevators automatically operates the elevator machine rooms’ independent ventilation or air conditioning system to maintain room temperature during fire fighters’ service operation.

a. The operating temperature must remain at or below the temperature established by the elevator equipment manufacturer’s specifications.

b. When elevator room operating temperature is exceeded, a supervisory signal is indicated at the MFACP.



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 101 9.6.5.2.

27. Emergency lighting energizes.


CONSULT WITH ELEVATOR DESIGNERS REGARDING METHOD TO BE USED FOR ELEVATOR TWO-WAY COMMUNICATION. REFER TO ANSI A17.1 RULES 211(a)(2) & (3) AND 211(b).
NFPA 1017.2.13.8 REQUIRES COMMUNICATIONS WIRING TO BE PROTECTED TO ENSURE AT LEAST 1 HOUR OF OPERATION IN THE EVENT OF A FIRE.

E. Personnel may use the elevator zoned two-way voice communication system master station (Section 142871) located at the MFACP to communicate with persons responsible for building safety.


F. User Programmable Control-By-Event Functions:

NEXT SEVERAL SUBPARAGRAPHS ARE EXAMPLES OF CONTROL-BY-EVENT FUNCTIONS. EDIT TO SUIT. ROUTINE OPERATION OR MONITORING PORTIONS OF AN HVAC SYSTEM SHOULD PART OF A BUILDING’S DIRECT DIGITAL CONTROL SYSTEM IF AVAILABLE.

1. Operation of photo cell on building ________ causes activation of exterior lighting on and activation of fence lighting, parking lot lighting and street lighting.

2. Activation of high level alarm contacts in sewage pump control panel is indicated by a supervisory signal and visible indicator at the MFACP.

3. The door status conditions (open, closed) in building ________ are indicated by visible indicators at the MFACP. Doors located on the First Floor, Lobby, may be unlocked with commands from the MFACP.

4. The computer room (first floor):

a. Air conditioning unit status is indicated by a supervisory signal and visible indicators at the MFACP.

b. Water alarm status is indicated by a supervisory signal and visible indicators at the MFACP.

REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 75 6-2.2.

c. Electric power status to the interlock and shutdown devices is indicated by a supervisory signal and visual indicators at the MFACP.


G. User Programmable Automatic Time-Initiated Functions (Start/Stop, On/Off, Secure/Access, etc.):

NEXT TWO SUBPARAGRAPHS ARE EXAMPLES OF AUTOMATIC TIME-INITIATED FUNCTIONS. EDIT TO SUIT. ROUTINE BUILDING OPERATION FUNCTIONS SHOULD BE PART OF A BUILDING’S DIRECT DIGITAL CONTROL SYSTEM IF AVAILABLE.

1. Exterior building lighting on buildings ________ may be energized and de-energized at times selected by facility personnel.

2. Parking lot lighting fixtures HPS-1 thru HPS-6 are energized from 6 p.m. to 1 a.m., Monday thru Friday.
H. An authorized person manually resets the system at the MFACP at conclusion of alarm condition. When an alarm condition is corrected, a display occurs at the MFACP stating the assigned reset message for the point in alarm with the date, time and reset suffix.

1. Manually resetting the system requires only one operation.

2. Resetting the system does not disturb system control points or functions.
I. Primary and Secondary Power Supplies:

1. Failure of primary power supplies automatically transfers the affected portions of the system to the secondary power supplies:



EDIT NEXT TWO SUBPARAGRAPHS FOR ITEMS NOT REQUIRED, OR THAT CANNOT BE ENERGIZED BY THE SECONDARY POWER SUPPLIES.

a. Initiating, notification, visual indication, and supervisory functions of the system are transferred without loss to the secondary power supplies.

1) Ground fault indication, and battery trouble conditions, are not required to transfer to the secondary power supplies.

b. System power requirements are transferred to the secondary power supplies except door hold open devices, door lock releases, controls for selected HVAC equipment, fire dampers, and smoke dampers.

c. Audible and visible indication of alarm condition when operating system on secondary power supply is:

OMIT SUBPARAGRAPH BELOW IF NOT APPLICABLE.

1) Performance of each ICU’s assigned audible and visible alarm functions.

2) Sounding of the MFACP’s audible alarm.

3) Illumination of the MFACP’s system alarm lamp or flashing display.

4) Display of assigned message.

THE TIME PERIOD OF 24 HOURS IN SUBPARAGRAPH BELOW MAY BE REDUCED TO 4 HOURS IF A DIESEL-ALTERNATOR SYSTEM MEETS THE REQUIREMENTS OF NFPA 72 1-5.2.6(b) AND 1-5.2.10.

2. Utilizing the secondary battery power supplies, the system operates under maximum quiescent load (system functioning in a non-alarm condition) for 24 hours and then is capable of operating all alarm notification appliances used for evacuation or to direct aid to location of an emergency for 5 minutes.

a. At the end of the time period the secondary battery power supplies also have capacity to operate the rolling fire shutters, fire door and heat and smoke roof vent emergency electric release devices.

1) The maximum power required to operate each heat and smoke roof vent emergency electric release device is 2.5 amperes at 24vdc for 1 minute.



INCLUDE SUBPARAGRAPH BELOW IF THE TIME PERIOD OF 24 HOURS PREVIOUSLY SPECIFIED HAS BEEN REDUCED TO 4 HOURS.

b. The secondary supply, in addition to the battery standby power supplies, also includes connection to an automatic starting diesel-alternator system which will operate the system for 24 hours.

3. Upon restoration of primary power supply, the system reverts to normal operation without loss, attendant intervention, or manual re-start procedures.
J. Monitoring Integrity of Installation Conductors and Other Signaling Channels

1. Performance of Signaling Line Circuits:



OTHER CLASSES AND STYLE ARE AVAILABLE THEN THOSE INDICATED BELOW. REFER TO NFPA 72, TABLE 3-6. OPTICAL FIBER CABLES ARE ONLY AVAILABLE STYLE 4 OR 7. ELECTRONIC CABLES ARE AVAILABLE FOR ALL STYLES.

a. Circuits from MFACP to ICU’s: NFPA 72, Class A, Style 7. A print-out and display occurs to identify trouble conditions.

b. Circuits from MFACP and ICU’s to Addressable Devices: NFPA 72, Class B, Style 4. A print-out and display occurs to identify trouble conditions.

2. Performance of Initiating Device Circuits:



OTHER CLASSES AND STYLES ARE AVAILABLE OTHER THAN THOSE INDICATED IN SUBPARAGRAPH BELOW. REFER TO NFPA 72 TABLE 3-5. OMIT REFERENCE TO SPRINKLER IF NOT APPLICABLE.

a. Circuits from MFACP and ICU’s to Initiating Devices (Fire Alarm, Sprinkler): NFPA 72, Class B, Style C. A print-out and display occurs to identify trouble conditions.

3. Performance and Capabilities of Notification Appliance Circuits:

OTHER CLASSES AND STYLES ARE AVAILABLE OTHER THAN THOSE INDICATED IN SUBPARAGRAPH BELOW. REFER TO NFPA 72 TABLE 3-7.

a. Circuits from MFACP and ICU’s to Notification Appliances: NFPA 72, Class B, Style Y. A print-out and display occurs to identify trouble conditions.

4. Monitoring Integrity of Power Supplies:

a. Primary and secondary power supplies are monitored for presence of voltage at the point of connection to the system. Failure of either supply results in a system trouble condition.

b. An audible and visible alarm and display indicates failure of the primary (main) power supplies, within the system, at the MFACP.

1) Each primary power supply trouble condition is also indicated at the FMCMS as a building (common) trouble condition.

c. Each system also monitors its secondary battery power supplies for battery trouble conditions (low voltage/no batteries, high current and charging current).

1) Each system battery trouble condition is also indicated at the FMCMS as a building (common) trouble condition.


K. Interconnection of Fire Safety Control Functions:

SUBPARAGRAPHS BELOW RELATE MOST CLOSELY WITH THE PRECEDING SUBPARAGRAPHS SPECIFYING LIFE SAFETY CONTROL-BY-EVENT FUNCTIONS UPON ALARM CONDITION. REFER TO NFPA 72 3-9 AND NFPA 101 9.6.5.2.
SHOW RELAY OR APPLIANCE AND WIRING THERETO WITHIN THREE FEET OF THE EQUIPMENT THAT PERFORMS FIRE SAFETY FUNCTIONS (BUILDING AND FIRE CONTROL FUNCTIONS THAT ARE INTENDED TO INCREASE THE LIFE SAFETY FOR OCCUPANTS OR TO CONTROL THE SPREAD OF FIRE)

1. A listed relay or other listed appliance connected to the fire alarm system is used to initiate control of protected premises fire safety functions and is located within 3 feet of the controlled circuit or appliance.

a. The installation wiring between the fire alarm control unit and the relay or other appliance is monitored for integrity.

b. Relays and appliances that operate on loss of power are considered self-monitoring for integrity.

2. The method(s) of interconnection between the fire alarm system and controlled electrical and mechanical systems is monitored for integrity and is achieved by one of the following recognized means:

a. Electrical contacts listed for the connected load.

b. Listed digital data interfaces, such as serial communication ports and gateways.

c. Other listed methods.

3. Fire safety functions do not interfere with other operations of the fire alarm system.

a. Fire safety function control devices and gateways are listed as compatible with the fire alarm control unit so as to prevent interference with control unit operation caused by controlled devices and to ensure transmission of data to operate the controlled devices.



INDICATE ON DRAWINGS FIRE SAFETY CONTROL FUNCTIONS THAT REQUIRE MANUAL CONTROL.

4. Controls provided specifically for the purpose of manually overriding automatic fire safety functions provide visible indication of the status of the associated control circuits.

a. Status indicators for emergency equipment and fire safety functions are arranged to reflect the actual status of the associated equipment or function.

5. Where the fire alarm system is a component of a life safety network, and it communicates data to other systems providing life safety functions:

a. The path for communicating data is monitored for integrity, including the physical communication media and the ability to maintain intelligible communications.

b. Data received from the network does not affect the operation of the fire alarm system in any way other than to display the status of life safety network components.

c. Where non-fire alarm systems are interconnected to the fire alarm system using a network or other digital communication technique; a signal (for example, heartbeat, poll, ping, query) is generated between the fire alarm system and the non-fire alarm system. Failure of proper receipt by the fire alarm system of confirmation of the transmission indicates a trouble condition.

NEXT SEVERAL PARAGRAPHS PERTAIN TO FIRE PROTECTION SYSTEM SUPERVISORY SIGNAL SERVICE. REFER TO NFPA 72 2-6, 2-7, 2-9, 3-8.3.3, NFPA 101 9.7.2, AND NYSUFP&BC 1060.4(e), 1060.5(f)(2).

L. Sprinkler System Alarm and Supervision:



SHOW SPRINKLER WATER FLOW ALARMS CONNECTED TO SPRINKLER WATER FLOW ALARM ZONES. DO NOT CONNECT SPRINKLER WATER FLOW ALARMS ON SAME ZONE WITH OTHER TYPE INITIATING DEVICES. REFER TO NFPA 13 3-10.2, 5-15.1.6 AND NFPA 72 3-8.3.2.4.

1. Flow of water through a waterflow fire alarm switch causes a system alarm.



SHOW SPRINKLER CONTROL VALVE SUPERVISION CIRCUITS CONNECTED TO SPRINKLER CONTROL VALVE SUPERVISION ZONES.

2. Supervision of sprinkler system signal attachments (sprinkler valve supervisory switches, pressure switches, etc.) are arranged to indicate circuit trouble and supervisory signal conditions at the MFACP for each circuit.

a. Removal of covers from water flow alarm switches indicates trouble conditions at the MFACP.

3. Control valves in the sprinkler system are supervised to initiate 2 separate and distinct signals at the MFACP, indicating movement of the valve from its normal position.

a. The off-normal signal is initiated during the first 2 revolutions of a hand wheel or during 1/5 of the travel distance of the valve control apparatus from its normal position.

b. The second signal indicates restoration of the valve to its normal position. (The off-normal signal remains until the valve is restored to its normal position).


M. Supervision of Pressure Sources Associated with Fire Suppression Systems:

1. Pressure sources are supervised to initiate two separate and distinct signals, one indicating that the required pressure has been increased or decreased, and the other indicating restoration of the pressure to its required value.

a. A pressure supervisory signal initiating device for a pressurized limited water supply, such as a pressure tank, indicates both high and low pressure conditions. A signal is obtained where the required pressure is increased or decreased 10 psi from the required pressure value.

REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 72 2-9.2(b).

b. A pressure supervisory signal initiating device for dry-pipe sprinkler system indicates both high and low pressure conditions. A signal is obtained when the required pressure is increased or decreased 10 psi from the required pressure value.



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 13 4-3.2.3.

c. A pressure supervisory switch for non-interlock or double interlock preaction sprinkler system initiates a signal when the pressure is not maintained at 7 psi.

d. A steam pressure supervisory initiating device indicates a low pressure condition. A signal is obtained where the pressure is reduced to a value that is 110 percent of the minimum operating pressure of the steam operated equipment supplied.

FOR PARAGRAPH BELOW REFER TO NFPA 72 2-9.4.

N. Supervision of Water Levels Associated with Fire Suppression Systems:

1. Water storage containers associated with fire suppression systems are supervised to obtain two separate and distinct signals, one indicating that the required water level has been lowered or raised and the other indicating restoration.

a. A pressure tank supervisory initiating device detects both high and low water level conditions. A signal is initiated when the water level falls 3 inches or rises 3 inches.

b. A supervisory signal initiating device for other than pressure tanks initiates a low-water level when the level falls 12 inches.

2. Water storage containers exposed to freezing conditions are supervised to initiate 2 separate and distinctive signals, one indicating that the temperature of the water has decreased to 40 degrees F, and the other indicating restoration to a temperature above 40 degrees F.


FOR PARAGRAPH BELOW REFER TO NFPA 20 CHAPTER 6 & 7.

O. Supervision of Electric Motor Driven Centrifugal Fire Pumps:



EDIT LOCATION OF FIRE PUMP CONTROLLER LOCATION TO SUIT PROJECT.

1. Activation of contacts in the fire pump controller in Fire Pump Room are indicated by an audible signal at the MFACP and a visible indicator in the RA/CC. Separate indication for each of the following conditions:

a. Main power source available visible indicator (visible indicator, constantly illuminated, demonstrating that operating voltage is available to the contactor coil).

b. Controller connected to alternate source (controller has been transferred to the alternate source, alternate source supplying power to the controller).

c. Disconnecting means is open.

d. Loss of alarm power sources.

e. Controller has operated into a motor running condition (fire pump running).

f. Loss of line power on line side of fire pump controller, in any phase (all phases monitored).

g. Phase reversal on line side of fire pump controller.

h. Automatic transfer switch isolating switch open.

2. Switch at MFACP allows attendant to start fire pump for non-automatic continuous operation independent of the pressure-actuated switch. Remote station switch cannot stop the fire pump.

FOR PARAGRAPH BELOW REFER TO NFPA 20 CHAPTER 8 & 9, AND NFPA 70 695-4(b)(5).

P. Supervision of Diesel Engine Driven Centrifugal Fire Pumps:



EDIT LOCATION OF FIRE PUMP LOCATION TO SUIT PROJECT.

1. Activation of contacts in the engine controller in the Fire Pump Room are indicated by an audible signal at the MFACP and a visible indicator in the RA/CC. Separate indication for each of the following conditions.

a. Engine running.

b. The controller main switch has been turned to off or manual position.



SEVERAL ENGINE CONDITIONS ARE REQUIRED TO BE MONITORED AT THE CONTROLLER. REFER TO NFPA 20 9-4.1.3 IF IT IS DESIRED TO HAVE ALL THE CONDITIONS SEPARATELY INDICATED AT THE MFACP INSTEAD OF A COMMON SIGNAL SPECIFIED IN PARAGRAPH BELOW. REFER TO NFPA 20 9-4.2(3).

c. Trouble on the controller or engine (common signal).

2. Switch at MFACP allows attendant to start fire pump for non-automatic

continuous operation independent of the pressure-actuated switch. Remote station switch cannot stop the fire pump.


FOR PARAGRAPH BELOW REFER TO NFPA 72 2-9.5 AND 3-8.3.3.1.1.

Q. Supervision of Room Temperature: A temperature supervisory device in areas exposed to freezing conditions associated with water automatic fire suppression systems indicates a decrease in water temperature to 40 degrees F and its restoration to above 40 degrees F.

1. Low temperature is indicated by an audible alarm at the FCS and visible indication in the RA/CC for:

ADD ADDITIONAL LOCATIONS WHERE TEMPERATURE SHOULD BE MONITORED

a. Fire pump area.

b. Valve closets.
IN PARAGRAPH BELOW STATE THE SPECIFIC TYPES OF AUTOMATIC FIRE SUPPRESSION SYSTEMS (CARBON DIOXIDE, HALON, FOAM, WET CHEMICAL, DRY CHEMICAL, WATER WASH, ETC.). REFER TO NFPA 72 3-8.3.2.5, 3-8.3.3, 3-8.3.4.1, 3-8.4.3 AND NYSUFP&BC 1060.7. OMIT IGU’S FOR SINGLE PANEL PROJECT.

R. The system operates in conjunction with automatic fire suppression systems (AFSS’s).

1. Alarm and trouble conditions in the AFSS’s are indicated at the MFACP and at the ICU’s to which the AFSS’s are connected.

2. A supervisory signal at the MFACP indicates off-normal condition and its restoration to normal for each AFSS (each AFSS is separately reset at its own control panel).



REFERENCE FOR SUBPARAGRAPH BELOW IS NFPA 96 7-4, 7-6, 7-7. SHOW THE SHUT OFF SCHEME ON THE DRAWINGS AND SPECIFY PRODUCTS TO SUIT.

3. Where alarm condition is initiated by a cooking operation AFSS, all sources of fuel and electric power to the equipment associated with the AFSS are automatically shut off.

4. Operation of a disconnect switch which allows the system to be tested without activating the AFSS causes a trouble condition to be indicated at the FCS.
FOR PARAGRAPH BELOW REFER TO NFPA 72 3-8.3.4.1.

S. Supervision of All Fire Suppression Systems for Tampering:

1. In addition to the specific supervision functions of each fire suppression system, each system also indicates trouble condition at the MFACP whenever components of the system are tampered with, opened or removed, including:

a. Removal of covers from junction boxes on the outside of buildings.

b. Valves installed in the connection between a signal attachment and the fire suppression system to which it is attached.

c. Operation of disconnect switches which are used to allow system testing without activating the fire suppression system.

  1   2   3


The database is protected by copyright ©dentisty.org 2016
send message

    Main page